• Standard Sprinklers

A fire sprinkler is the component of a fire sprinkler system that discharges water when the effects of a fire have been detected, such as when a predetermined temperature has been exceeded. Fire sprinklers are extensively used worldwide, with over 40 million sprinkler heads fitted each year. In buildings protected by fire sprinklers, over 99% of fires were controlled by fire sprinklers alone



• Fire Sprinkler System

Each closed-head sprinkler is held closed by either a heat-sensitive glass bulb or a two-part metal link held together with fusible alloy. The glass bulb or link applies pressure to a pip cap which acts as a plug which prevents water from flowing until the ambient temperature around the sprinkler reaches the design activation temperature of the individual sprinkler head. In a standard wet-pipe sprinkler system, each sprinkler activates independently when the predetermined heat level is reached. Because of this, the number of sprinklers that operate is limited to only those near the fire (in reality, normally one or two will activate), thereby maximizing the available water pressure over the point of fire origin. This also minimizes the water damage to the building.

A sprinkler activation will do less damage than a fire department hose stream, which provide approximately 900 liters/min (250 US gallons/min). A typical sprinkler used for industrial manufacturing occupancies discharge about 75-150 litres/min (20-40 US gallons/min). However, a typical Early Suppression Fast Response (ESFR) sprinkler at a pressure of 50 psi (340 kPa) will discharge approximately 100 US gallons per minute (0.0063 m3/s). In addition, a sprinkler will usually activate between one and four minutes, whereas the fire department typically takes at least five minutes to arrive at the fire site after receiving an alarm, and an additional ten minutes to set up equipment and apply hose streams to the fire. This additional time can result in a much larger fire, requiring much more water to extinguish.



• Fire Sprinklers

Fire sprinklers can be automatic or open orifice. Automatic fire sprinklers operate at a predetermined temperature, utilizing a fusible element, a portion of which melts, or a frangible glass bulb containing liquid which breaks, allowing the plug in the orifice to be pushed out of the orifice by the water pressure in the fire sprinkler piping, resulting in water flow from the orifice. The water stream impacts a deflector, which produces a specific spray pattern designed in support of the goals of the sprinkler type (i.e., control or suppression). Modern sprinkler heads are designed to direct spray downwards. Spray nozzles are available to provide spray in various directions and patterns. The majority of automatic fire sprinklers operate individually in a fire. Contrary to motion picture representation, the entire sprinkler system does not activate, unless the system is a special deluge type.

Open orifice sprinklers are only used in water spray systems or deluge sprinklers systems. They are identical to the automatic sprinkler on which they are based, with the heat sensitive operating element removed.

Automatic fire sprinklers utilizing frangible bulbs follow a standardized color-coding convention indicating their operating temperature. Activation temperatures correspond to the type of hazard against which the sprinkler system protects. Residential occupancies are provided with a special type of fast response sprinkler with the unique goal of life safety.