Phase Correction Relay :
Protection of 3 Phase devices against Over voltage,Under voltageor unbalance supply is one of the major issue in electrical systems.
For safe running of 3-phase devices, special protections that keep a continuous watch on supply conditions are very essentials. The major cause of maxium load burn-out is overloading which occurs due to unbalance supply
'PROTONs PHASE CORRECTOR RELAY' offer following protections along with 3 digit display showing R-Y,Y-B,BR voltages in scanning mode with precise accuracy.
LOW/HIGH voltage tripping to ensure trouble free running of 3-phase Loads. Single phasing & Unbalance protection.
Phase correction RELAY 'R2' which operates only when phase
sequence changes.
Working :
In the normal run mode, display shows Voltages Vry,Vyb,Vbr for 10 sec. each If the supply is within the range (No faults)then display shows count down for time set in the set point ( default 10 sec) & after that Relay will be ON. If OV/UV/SPP/Reverse Phase or unbalance occurs in the supply then Relay will be OFF & corresponding fault LED starts blinking.Hysterisis betwen Cut off & cut in is 10V for OV & UV. Note that for SPP & Unbalance LED is not blinking but message appears on display at end of scanning. but display shows particular fault"rP" at the end of scanning.All the faults are indicated by message.
If phase reversal occurs then Relay 1 will be off & after time delay Relay 2 will be ON.
If phase sequence is Ok then again Relay 1 will be ON.
OV,UV,SPP is applicable for both relays
SET POINTS :
- To set Under voltage set point press FUN key once,display shows 'uV' again press FUN key then the set point is viewed (default 350V)now user can set the
UV set point using arrow keys.
- To set Over voltage set point press FUN key till display shows 'oV' again press FUN key then the set point is viewed(default 460V) now user can set the OV set point using arrow keys.
- To set On delay set point press FUN key till display shows 'dly' again press FUN key then the set point is viewed(default 10sec.)now user can set the
on time for relay using arrow keys.
To decide maximum imbalance tolerable between phase voltages(Imbalance set point) press FUN key till display shows 'ub' again press FUN key then the set point is viewed(default 40V)now user can set imbalance set point using arrow keys.
SET POINTS:
IMP.NOTE: After set point entered,the system goes into Run mode
automatically after 5 sec.The setpoint is stored automatically.
also if a set point is changed & FUN key pressed again then also
set point is saved in memory.