javascript slider

Single Phase Preventer 2

Protection of induction motors against single phasing or reverse phasing or unbalance supply is one of the major problems in electrical systems. For safe running of 3-phase motors, special protections that keep a continuous watch on supply conditions are very essentials. The major cause of maxium motors burn-out is overloading which occurs due to unbalance supply or single phasing. Phase failure occurs in case of fuse blown-off, loose connections or loss of phase from supply itself.
'PROTONs MULTIFUNCTION RELAY - SPP 2' offer these protections along with LOW/HIGH voltage tripping to ensure the trouble free running of 3-phase motors.

SALIENT FEATURES :

  • Operates on the principle of sensing negative sequence components of the system.
  • Suitable for the protections of motors of any H.P.
  • Protection against single phasing, reverse phasing, unbalance supply, under/over voltage.
  • Variable trip voltage setting for under/over voltage protection. Fixed unbalance trip setting at 40 volts.
  • No separate auxiliary supply required.
  • Individual trip indication for under voltage, over voltage, single phasing, reverse phasing and indication for output relay ON.
  • Auto reset type voltage hysterisisgap for tripping on under/over voltage.

TECHNICAL SPECIFICATION :

* Due to continuous change, specifications are subject to change without notice.

System Supply : 415 VAC, Three phase +/- 10%
Output Contacts : One changeover ( C-NO-NC)
Output contact rating : 5 Amps at 230 V AC.
Trip Time delay : 2-3 seconds.
Variable Voltage Setting : For Under voltage,
330 TO 370 VAC.
For Over voltage,
430 TO 470 VAC.
Reset Mode : Auto reset.
Trip Indications : For over voltage, under voltage, single phasing and reverse phasing and relay ON indication.
Unbalance trip setting : Fixed at 40 Volts between any two phases..
Temperature range : -5 0C to 60 0C.
Relative humidity : 95% R.H.
Mounting : Din rail.
Base mounting dimensions 55 (W) x 65 (L) x 125 (D) mm.
Auxiliary Supply : 24 V DC, +/- 10% (optional feature)

APPLICATION :

Electrical Panels. Compressor motors.
Electrical Test benches. Submersible pumps.
Genset panels. Cold storages.
Package unit and central air Conditioning Plants.

WIRING DRAWING :